Date:      Mon, 8 Oct 2007 02:36:05 +0200
From:      Pieter de Goeje <pieter@degoeje.nl>
To:        freebsd-questions@freebsd.org
Cc:        Gary Kline <kline@tao.thought.org>, Erich Dollansky <oceanare@pacific.net.sg>
Subject:   Re: what kind of UPS will work best?
Message-ID:  <200710080236.05888.pieter@degoeje.nl>
In-Reply-To: <20071007194446.GA69551@thought.org>
References:  <20071006231203.GA65801@thought.org> <47084E80.3010003@pacific.net.sg> <20071007194446.GA69551@thought.org>

next in thread | previous in thread | raw e-mail | index | archive | help
On Sunday 07 October 2007, Gary Kline wrote:
> 	First, thank to both you and Bart for your cmments.  You were
> 	*right* about the price.  Can I assume that a ballpark would be
> 	400W for each server?  (My wife is right: I've got to cut back to
> 	three computers:-)  I've found one APC 2200VA with a 17minute
> 	uptime.  3 times 400W, yes?

I think this is overkill. Some time ago I was wondering the same thing and to 
verify my guess on the overall power usage of my servers I bought a VA/Watts 
meter (EUR. 39,-). Turns out average wattage is about 90watts per server idle 
and max 130watts under load. On powerup they will use a max. of 180watts for 
less than a second. The servers are simple dual cores with about 2 harddisks 
each. (no screens or other devices attached) Also, the powerfactor was ~0,95 
so that means that for every Watt of apparent power (VA) almost a Watt of 
real power was used. Thus, for my servers I would need something like a 
500Watt/600VA UPS.

So my advice is: don't guess but measure.

Cheers,
Pieter de Goeje



Want to link to this message? Use this URL: <https://mail-archive.FreeBSD.org/cgi/mid.cgi?200710080236.05888.pieter>